Access control and the fire alarm: what has to happen on activation

Updated

This is the part of an access control job that is not a matter of preference. Get it wrong and you have installed a system that keeps people in.

The principle

Access control holds doors closed. Escape needs doors open. Where those two meet, the fire strategy wins. gov.uk's guidance on fire safety and evacuation plans requires your plan to show a clear passageway to all escape routes, clearly marked routes that are as short and direct as possible, enough exits and routes for everyone to escape, and emergency doors that open easily (gov.uk). An access control design has to be consistent with that, and with the findings of your fire risk assessment.

We deliberately do not tell you which doors should release, on what signal, or with what fail-safe arrangement. That is a decision for your fire risk assessor and the fire alarm engineer for your specific building, and no website can make it for you. What we can tell you is that it must be decided, priced and documented.

What the interface actually is

In most buildings there is a physical link between the fire alarm panel and the access control system, so that on activation the doors covered by the strategy release. It is real engineering work: a monitored connection, defined behaviour for each door, commissioning with the alarm engineer present, and a record of the test. It is not a wire someone adds on the last afternoon of the install.

Terms your installer will use

Fail-safe and fail-secure
Whether a lock releases or stays locked when power is removed. Different doors in the same building can legitimately need different answers, which is exactly why it needs designing rather than defaulting.
Green break-glass unit
The manual emergency release next to a controlled escape door. Its presence, position and whether it is monitored are part of the design, not an afterthought.
Request to exit
The device that lets people leave normally without a credential. Its failure mode matters as much as the lock's.
BS 7273-4
The British Standard covering the actuation of release mechanisms for doors. We name it rather than link it because it is a published standard you buy from BSI, not a free web page. Ask your fire risk assessor whether it applies to your building and which critical category your doors fall into.

How to price it properly

  • Say in your enquiry that the system must interface with the fire alarm. Quotes that assume no interface will always look cheaper.
  • Ask who is responsible for the interface: the access control installer, the fire alarm company, or both, and who commissions it.
  • Ask for the test to be witnessed and recorded, and for the result to go in your fire safety records.
  • Send the design to your fire risk assessor before installation, and keep their response.
  • Check the interface at every fire alarm test after that. A door that stopped releasing three months ago is a defect nobody notices until it matters.

Intruder alarm interaction

The other common integration is the intruder alarm, so that a valid credential at the final door unsets the system and the last person out sets it. It is much less safety-critical than the fire interface but it is a real source of nuisance calls when it is done badly. Ask whether the integration is native between the two manufacturers or needs an interface module and a licence.

Questions, answered directly

Do access control doors have to release when the fire alarm sounds?

Escape routes have to work: gov.uk's fire safety guidance requires clear escape routes and emergency doors that open easily. Exactly which doors release, on what signal and with what fail-safe arrangement is a design decision for your fire risk assessor and fire alarm engineer for your specific building. Get it specified before installation and recorded afterwards.

What is a fail-safe lock?

One that releases when power is removed, as opposed to fail-secure, which stays locked. Different doors in the same building can properly need different behaviour, so it should be specified door by door in the design rather than applied as a default across the site.

Who signs off the fire interface on an access control system?

The design should be agreed with your fire risk assessor and the fire alarm engineer, commissioned with both systems present, tested, and the test recorded in your fire safety records. Make clear in the enquiry that an interface is required, otherwise quotes will exclude it and appear cheaper.

Get a per-door price, not a guess.

Two minutes of questions and access control installers who cover your postcode quote you directly. Free, no obligation.

Get access control quotes